Implementación y prueba en tiempo real de un esquema de disparo acelerado de segunda zona para relevadores de distancia no comunicados (Implementation and real time test of an accelerated zone 2 trip scheme for non-communicated distance relays)

German Rosas (grosaso@ipn.mx), Ricardo Mota (rmotap@ipn.mx)


Instituto Politecnico Nacional
This paper appears in: Revista IEEE América Latina

Publication Date: June 2012
Volume: 10,   Issue: 4 
ISSN: 1548-0992


Abstract:
This work describes an algorithm which allows the trip acceleration on zone 2 of non-communicated distance relays for cases where faults are located inside the protected line. The algorithm is based on the detection of remote breaker operation following a zone 2 fault detection by local distance relay and it uses as a basis the monitoring of changes on a proposed signal. This algorithm is evaluated using data from fault cases generated by an electromagnetic transients program for different fault and operation conditions of a test power system. Real time operation is validated by implementing the proposed algorithm into a distance relay model using generic data acquisition and signal processing hardware. This relay is then evaluated using a real time digital simulator RTDS and throughout the tests, the results show that proposed algorithm is able to provide accelerated zone 2 trips with reduced operating times than those issued by relays using conventional zone 2 trip.

Index Terms:
protective relaying, real time simulation, transmission lines   