|
Peak Withstand Current Test
- new device with clean contacts
- three-phase or two adjacent phases
- rated duration, or not less than 0.3 sec
Short-Time Withstand Current Test
new device with clean contacts
- three-phase or two adjacent phases
AFTER TESTS, switch must:
- exhibit no mechanical damage
- carry continuous rated current without exceeding temp-rise limits
- be capable of its rated switching duties
- if resistance increased by more than 20%, and contacts cannot be visually inspected, then additional temp rise test may be appropriate
|
Peak Withstand Current Test
Reference IEC 694
- three-phase or two adjacent phases
- return conductor parallel to blade and at same elevation
- length of return conductor at least equal to distance. between input and output terminals of the disconnector
[U £
52 kV]
see test arrangement (Fig. 4) for distances between input terminals and supports
[52 kV <
U]
see test arrangements (Figs. 5 and 6) for connections by flexible and rigid conductors
Short-Time Withstand Current Test
Reference IEC 694
- additional notes same as above
|
Peak Withstand Current Test [1 kV <
U]
- three-phase or two adjacent phases
- return conductor parallel to blade and at same elevation
- conductors must be unsupported for at least the open gap distance
- minimum duration: 10 cycles (0.167 sec)
- at any convenient voltage
Short-Time Withstand Current Test
new device
- three-phase or two adjacent phases
AFTER TESTS, the device must:
- exhibit no visible damage
- withstand at least 15 open-close cycles
If there are slight contact markings, then device must:
- carry continuous rated current without exceeding allowable temperature rise
- be capable of its rated switching duties
|
|
Temperature-Rise Tests
- stabilized when temp rise does not exceed 1 K/hour
- ambient air temp between 10°
C and 40°
C
- resistance before and after temp rise test shall not differ by more than 20%
- new device with clean contacts
- air movement less than .5 m/s
|
Temperature-Rise Tests
Reference IEC 694
- temp rise of main circuit is only applicable for disconnectors
|
Continuous Current Tests
[1 kV <
U]
- stabilized when 3 consecutive values of temp rise, at 30-min. intervals, show max. variation of 1 degree
- ambient air temp between 10°
C and 40°
C
- (no reference to before and after resistance)
- mount device in a room substantially free from drafts
- conductors at least four feet long
Switch Performance Test
design test - not used to establish overload rating
- 180% of rated current
- ambient air temperature between 25°
C and 30°
C
- duration: 8 hours
- temps considered stable if rise does not exceed 3% during last 4 hours of test
- pass test if device is suitable for operation at maximum speeds without cumulative mechanical damage
|