|
Short-Duration Power-Frequency Withstand
Reference to IEC 60-1
- maintain test voltage for 1 min.
- during wet test, if one disruptive discharge occurs on self-restoring insulation, then repeat test to pass
- test both wet and dry conditions
- atmospheric corrections, reference IEC 60-1
[U >
245 kV]
Reference to IEC 60-1
- maintain test voltage for 1 min.
- dry conditions only
|
Short-Duration Power-Frequency Withstand
[1 kV £
U ³
52 kV]
Reference to IEC 694 |
Power-Frequency Voltage Withstand
[1 kV £
U]
dry test:
maintain test voltage for 1 min.
apply 75% of voltage in one step, then gradually raise the voltage over 5 - 30 sec max.
maintain test voltage for 10 sec.
apply voltage as above
maintain test voltage for 10 sec raise voltage rapidly in not more than 20 sec
|
|
Lightning Impulse Withstand [all voltage levels]
Reference to IEC 60-1
- standard impulse: 1.2/50 m
s
- dry conditions only
- 15 impulses each test condition and each polarity
- to pass:
max. 2 discharges per series allowed on self-restoring insulation, AND no discharges on non-self-restoring insulation
OR to pass:
- 3 consecutive impulses on each polarity and condition with no discharges.
- if discharge occurs on self-restoring insulation, then 9 additional impulses with no discharges are required to pass.
|
Lightning Impulse Withstand [all voltage levels]
Reference to IEC 694
|
Lightning Impulse Withstand [1 kV £
U]
standard impulse: 1.2/50 m
s
dry conditions only
3 consecutive impulses, each polarity
to pass:
if one discharge occurs, then 9 additional consecutive impulses are required with no further discharges
Open Gap Withstand
Standard Test:
- test voltage 10% higher than rated one minute power freq. withstand voltage
- test voltage 10% higher than rated lightning impulse dry withstand voltage
- total of 6 impulses to each terminal: 3 positive polarity,
3 negative polarity, with other terminal and base grounded
- to pass:
same criteria as above
- flashover to ground during 3X9 series is a non-event
- only one flashover to ground is allowed per each 3X9 series
- Bias Test method (acceptable alternative) also cited for switches rated 362 kV and above
|
|
Switching Impulse Withstand
[U >
245 kV]
Reference to IEC 60-1
- standard impulse: 250/2500 m
s
- wet tests for outdoor gear only
- insulation between poles, dry test conditions only
[no reference to determination of withstand values]
Open Gap Withstand
Reference to IEC 60-1
- When open gap withstand voltage is higher than phase-to-earth withstand voltage, different test methods are used.
Preferred Method:
combined voltage tests
- Power-frequency voltage test: two different voltage sources, in out-of-phase conditions
- Impulse voltage test: rated impulse voltage applied to one terminal; complementary voltage from another source of opposite polarity is applied to other terminal
Alternate Method:
only one voltage source
- total test voltage applied between one terminal and earth; opposite terminal is earthed
ACCEPTANCE CRITERIA:
- No acceptance specifications given in IEC 694
|
Switching Impulse Withstand
[U³
300 kV]
- two classes: Class A & Class B
- classes depend on service conditions
Two test series:
- Table VIII of IEC 694 for rated withstand voltage to earth
- Second Test is either of:
- Class A
Table IV of IEC 694 for rated switching impulse withstand
b. Class B
Table X of IEC 694, with one terminal energized with switching impulse voltage across the isolating distance, and opposite terminal energized at power-frequency voltage U/Ö
3
|
Switching Impulse Withstand
- standard impulse: 250/2500 m
s
- both dry and wet (per IEEE 4-1978) tests required
- withstand voltage determined by "Up-and-Down Method," per C37.34 and IEEE 4-1978
Open Gap Withstand
- 3 applications of switching impulse voltage
- apply switching impulse withstand voltage on one terminal and apply bias voltage of 60 Hz on opposite terminal. Timing must be such that the polarity of one voltage crest is opposite from the polarity of the voltage crest on the other terminal of the switch.
ACCEPTANCE CRITERIA:
- no flashovers across open gap
OR
- if only one flashover occurs across the open gap, then 9 additional consecutive impulses are applied. One flashover to ground is permitted during the 3X9 series.
|
|
Partial Discharge Test
Reference to IEC 270 |
Partial Discharge Test
no tests required on the complete disconnector or earthing switch |
Partial Discharge Test
(No References or specifications cited) |
|
Corona Tests
(No References or specifications cited)
|
Corona Tests
(No References or specifications cited) |
Corona Tests
[121 kV £
U]
non-enclosed outdoor-switches
no atmospheric corrections as present
corona plumes and spikes shall not be visible at voltages lower than 1.10 times the line-to-neutral value of rated max. voltage
|
|
Dielectric Test on Auxiliary & Control Circuits
Reference to IEC 1180-1
Short-duration power-frequency withstand:
- test voltage is 2000 V
- duration 1 min.
- no disruptive discharge allowed
|
Dielectric Test on Auxiliary & Control Circuits
Reference IEC 694
|
Control Wiring Insulation Test
(No References or specifications cited)
|
|
Radio Interference Voltage
- switch both open and closed
- only for rated voltage (U) higher than 123 kV
- apply voltage of 1.1U/Ö
`
3
- pass if radio interference level is less than 2500 m
V
|
Radio Interference Voltage
Reference IEC 694, and:
- tests subject to special agreement between user and manufacturer
|
Radio-Influence Voltage
- switch both open and closed
- no atmospheric corrections at present
- apply voltage at rated power-frequency of device
(no duration or acceptable levels are cited) |